Event Recorder Printout of Three Mile Island Accident


Page 6





00:l0:19	Reactor Bui1ding Sump Pump B (WDL-P-2B) started.
(0410:56)


00:10:24	Reactor Coolant Makeup Pump A (MU-P-1A) tripped.
(0411:01)


00:10:27	Reactor Coolant Makeup Pump A (MU-P-1A) was started.
(0411:04)


00:10:28	Reactor Coolant Makeup Pump A (MU-P-1A) tripped.
(0411:05)


00:10:40	Reactor Bui1ding Sump high level alarm received.  Setpoint is
(0411:25)
		4.650 feet.



00:11:40	Reactor Coolant Makeup Pump A (MU-P-lA) was started.
(0412:17)



00:14:50	The Reactor Coolant Drain Tank rupture diaphragm (WDL-U26) failed.
(0415:27)


00:24:58	The operator requested computer printout of the Electromatic
(0425:35)
		Relief Valve (RC-RV2) outlet temperature.  The reading was 285.4F.


00:25:00	Intermediate Cooling System high radiation alarm annunciator
(0425:37)
Approximate	received at the Radiation Monitor Pane1.


00:36:08	Emergency Feedwater Pump 2B (EF-P-2B) was stopped.
(0436:45)


00:38:10	Reactor Bui1ding Sump Pump A (WDL-P-2A) was stopped.
(0438:47)


00:38:11	Reactor Building Sump Pump B (WDL-P-2B) was stopped.
(0438:48)


01:10:54	Reactor Building air cooling coils emergency discharge alarm
(0511:31)
		printed out.


- 6 -


[Home] [2] [3] [4] [5] [6] [7] [8] [9] [10] [11] [12] [13] [14] [15] [16] [TMI #2 Diagram]

E-Mail --Webmaster@disastercity.com


Back to Disaster City